Hard suction hose

5-inch (13 cm) hard suction hose with Storz fittings, mounted on an engine

Hard suction hose (alternatively, suction hose) is a specific type of fire hose used in drafting operations, when a fire engine uses a vacuum to draw water from a portable water tank, pool, or other static water source. It is built to withstand vacuum, rather than pressure, abrasion, and heat. In the United States, it is standard equipment according to the National Fire Protection Association standards for fire engines. It is used in both structural and wildland firefighting throughout the world, and is made in various diameters and connection types.

Usage

Main article: Drafting water

Hard suction hose, also known as a suction hose, is a specific type of rigid fire hose used in drafting operations. When using this technique, the fire engine draws water for fire fighting from an unpressurized supply, such as a portable water tank, pool, or other static water source, instead of drawing water from a pressurized water supply, such as a fire hydrant. Under complete vacuum conditions, a pump would lift water 33.9 feet (10.3 m), however pumps on fire apparatus are not capable of producing a high vacuum.[1]:388 Due to this limitation and friction loss, fire services do not recommend attempting to lift water more than 3 metres (9.8 ft).[2]

Hard suction hose may also be used to connect a fire engine to a hydrant. This practice is common in Australia,[2] but woven jacket fire hose is normally used for this purpose in the United States. Using hard suction hose in this manner requires that the fire engine be positioned carefully for the limited flexibility of the hose, and may require multiple firefighters due to the weight and bulk of the hose section.[3] In certain circumstances, it may be possible to use hard suction hose to draft from a hydrant with adequate water supply but a low flow rate.[4]

These hoses are built to withstand vacuum, rather than water pressure, abrasion, and heat. They are, therefore, constructed differently from the standard fire hose and have different end fittings. In the United States, they are standard equipment according to the National Fire Protection Association standards for fire engines. Since hard suction hose cannot be folded, it is typically mounted on the side of a fire engine, often opposite ground ladders.[5] Such hose is used in both structural and wildland firefighting throughout the world.[6][7]

Hard suction hose can also be used to extend the range of a water tender's dumping capability, if the fittings of the hard suction hose match those of the tender dumping water. This could be used to fill a portable dump tank not immediately adjacent to the water tender, from which another fire engine can draft. Since water movement during dumping relies on gravity, rather than mechanical pressurization, hard suction hose is useful for this task.[8]

Characteristics and construction

Hard suction hose differs from standard fire hose in both its construction and usage:

  1. It is rigid and generally scalloped. Often, such hose is manufactured using molded synthetic material (such as PVC) shaped into a series of rings.[9] This shape allows the hose to be somewhat flexible, without allowing it to collapse in on itself under suction, as a normal, woven-jacket fire hose would.[9]
  2. It uses suction gaskets. Gaskets in standard fire hose ("pressure gaskets") are designed to minimize the water leaking out between couplings. The gaskets connecting hard suction hose sections, pump, and strainer must instead prevent air from entering at the coupling, since that would spoil the vacuum and allow air into the pump intake.[10] Large diameter (4-inch (10 cm) or greater) hard suction hose will typically use Storz fittings, which are genderless. 3-inch (7.6 cm) or smaller hard suction hose will typically use threaded fittings. In each case, the hard suction hose connection will match the fittings of the pump intake and supply hose, so that hard suction hose can be used in place of supply hose as appropriate.
  3. It is short. Typically, hard suction hose comes in 10 feet (3.0 m) lengths, while fire hose comes in 50 and 100 feet (15 and 30 m) lengths.[11] Since a fire engine's pump only produces a partial vacuum, it is only recommended for lifting water 3 metres (9.8 ft) or less.[2] For this reason, and because each junction is an opportunity for a crack or imperfect seal to spoil the vacuum, it is rare to see many sections of hard suction hose connected together.
  4. It is not designed for use in fire streams.[12] The airtight nature of hard suction hose, necessary for drafting, renders the hose unsuitable for the high pressure water flow needed to spray a pressurized stream of water on a fire.[13] Thus, hard suction hose is tested for the ability to "prevent collapse under vacuum conditions" rather than its ability to function as an attack hoseline.[11]

Hard suction hose predates steam or gas powered fire engines and has been available since at least 1888, sometimes referred to as "spiral suction hose".[14]

Diameter

Hard suction hose comes in multiple sizes, from 2 to 6 inches (5.1 to 15.2 cm) in diameter.[9] Large diameter hose are carried on full-size fire engines, but smaller diameters of hard suction hose can be carried on apparatus with smaller fire pump ratings, such as wildland fire engines. In the United States, NFPA 1901 requires engines to have hard suction hose that matches the engine's pump rating.[11] For example, an engine with a 1,000-US-gallon (3,800 l) per minute pump is required to carry 5-inch (13 cm) or larger hose,[1]:181 while a wildland fire engine will typically carry 2-to-2.5-inch (5.1 to 6.4 cm) hard suction hose.[15]

The United Kingdom, has a standardised range of metric hose diameters: 7, 9, 12.5 and 15 cm (2.8, 3.5, 4.9 and 5.9 in), with the two smallest diameters sometimes used twined to provide adequate flow rates.[16] Within this range, the 7 centimetres (2.8 in) hoses are fitted with "Instantaneous Couplings"; the 12.5 and 15 centimetres (4.9 and 5.9 in) hoses have Storz couplings; and the 9 centimetres (3.5 in) hose comes in two types, one with "Instantaneous Couplings" and one with Storz fittings.[16] Fire Service Manuals provide tables of maximum volumetric flow rates for a given pump pressure, hose diameter and total hose length. The use of these tables, is to facilitate the selection of suitable hoses, taking into account the frictional losses caused by transporting water through the strainer, hoses, pump and fire fighting nozzles, to draft water from source to the fireground.[16]

Strainers

Strainer with 5-inch (13 cm) Storz fitting
Strainer on a 2.5-inch (6.4 cm) diameter hard suction hose

When being used in a drafting operation from a pool, portable water tank, or other uncovered water source, the length of hard suction hose farthest from the pump is usually attached to a strainer, to keep foreign objects in the water from being pulled into and damaging the pump.[11] If used in a pond, stream, or other body of water, an appropriate flotation device must be used to keep the strainer below the surface and above the bottom, so that neither mud nor air are sucked into the fire engine's pump.[11] When drafting from a solid-bottomed tank or pool, a strainer can safely rest on the bottom without suctioning mud into the fire engine's pump.

The United Kingdom official guidance is to:[17]

See also

References

  1. 1 2 Mahoney, Gene (1986). Introduction to Fire Apparatus and Equipment. PennWell Books. ISBN 0-912212-12-8. Retrieved 2008-08-10.
  2. 1 2 3 Fire & Emergency Services Authority of Western Australia (2008). "GL 08 Hard Suction (Storz) connections" (pdf). Retrieved 2009-08-19.
  3. International Association of Fire Chiefs (2007). Industrial Fire Brigade: Principles and Practice. Jones & Bartlett. p. 492. ISBN 0-7637-3502-7. Retrieved 2009-08-19.
  4. Lamm, Willis (2001). "Drafting From Low Pressure Hydrants". firehydrant.org. Retrieved 2009-08-19.
  5. Shapiro, Larry (1999). Pumpers: Workhorse Fire Engines. MBI Publishing. p. 25. ISBN 0-7603-0672-9. Retrieved 2009-08-30.
  6. "Vehicle Mounted Pump - Godiva World Series WT2010 and WT4010". Hampshire Fire and Rescue Service. Retrieved 2009-08-19.
  7. "Draft Number: DZ 4509, New Zealand Fire Service Firefighting Water Supplies Code of Practice" (PDF). 2008-02-05. Archived from the original (pdf) on May 26, 2010. Retrieved 2009-08-19.
  8. Eckman, William F. (1994). The Fire Department Water Supply Handbook. PennWell Books. p. 285. ISBN 0-912212-35-7. Retrieved 2008-08-10.
  9. 1 2 3 The Firefighter's Handbook: Essentials of Firefighting and Emergency Response. Delmar Publishers. 2000. p. 209. ISBN 0-7668-0581-6. Retrieved 2008-08-10.
  10. "FAQ's". Jerome Fire Equipment Co., Inc. Retrieved 2008-08-06. "Suction gaskets have a flap on the outer rim, facing the outside. The coupling torque to assemble mating suction couplings is higher so that these flaps on mating couplings are pressed together initially, sealing out the outside air, so that the draft can be started."
  11. 1 2 3 4 5 Sturtevant, Thomas B. (2004). Introduction to Fire Pump Operations. Thomas Delmar Learning. ISBN 0-7668-5452-3. Retrieved 2008-08-10.
  12. "Manual: LDH Hard Suction Hose" (PDF). Task Force Tips. 2007-03-21. Retrieved 2008-08-06.
  13. Stacey, John W. (2001). "Report of the Committee on Fire Hose" (pdf). National Fire Protection Association. Retrieved 2009-08-19. "Positive pressure requirements for hard suction hose were deleted as using hard suction hose for positive pressures is not a practical application."
  14. The Goulds M'f'g. Co's. illustrated ...: catalogue and price list, of pumps, engines ... The Goulds Mfg. Co. 1888. p. 177. Retrieved 2009-08-30.
  15. National Wildfire Coordinating Group (NWCG). "Glossary of Wildland Fire Terminology". Retrieved 2009-08-19.
  16. 1 2 3 HM Fire Service Inspectorate (2001). Chapter 7: "Pre-Planning" in: Fire Service Manual, Volume 1, Fire Service Technology, Equipment and Media: Hydraulics, Pump and Water Supplies. London: the Stationery Office. ISBN 0-11-341216-9.
  17. HM Fire Service Inspectorate (2001). Chapter 6: "Pump Operation and the Distribution of Water on the Fireground" in: Fire Service Manual, Volume 1, Fire Service Technology, Equipment and Media: Hydraulics, Pump and Water Supplies. London: the Stationery Office. ISBN 0-11-341216-9.

This article is issued from Wikipedia - version of the 10/2/2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.